top of page

PRODUCT DETAILS

image.png

Container system
X-series

Water and electricity isolation design

Cabinet and miner water and electricity isolation design
Power supply on the front of the cabinet, and run the water in the back to avoid equipment damage and life safety accidents caused by water splashing into the electrical components.
Container water and electricity isolation design
①The floor is elevated and water pipes are laid below
②The pump room is isolated design to avoid equipment damage and life safety accidents caused by abnormal water leakage in the water system.

High temperature design

The miner water inlet temperature up to 75℃

High temperature easier cooling,and adapt to high temperature application scenarios.
Can provide higher quality hot water.

Non-leakage quick connectors design

The use of non-leakage quick connectors, maintenance of the miner does not have to worry about the short circuit caused by the splash of water under pressure when the pipeline is disconnected, and improves the reliability and efficiency of the miner's loading and unloading

Wide voltage design

Miners and containers wide voltage design

rated voltage: 3 phase 380V~480V
rated frequency: 50/60Hz

X Series Solution 1000/1600/2400kw
Product Compoents

XS1000

1000kW

• 100 × Miner Slot(2U)

• 5 × Hydro Cooling Rack

• Exposed Pipeline System

• Build-In CDU

• Build-In Switchgear

• Emergency Stop Button

• Ventilation System

• Lighting,Cameras and

Smoke Alarm

透明背景.png

XS1600

1600kW

• 160 × Miner Slot(2U)

• 8 × Hydro Cooling Rack

• Underfloor Pipeline System

• Build-In CDU

• Build-In Switchgear

• Emergency Stop Button

• Ventilation System

• Lighting,Cameras and

Smoke Alarm

xs1600.png

XS2400

2400kw

• 240 × Miner Slot(2U)

• 12 × Hydro Cooling Rack

• Exposed Pipeline System

• Build-In CDU

• Build-In Switchgear

• Emergency Stop Button

• Ventilation System

• Lighting,Cameras and

Smoke Alarm

image.png

Product details

X Series Solution-1000kW

Technical Specification

image.png

Physical

Model 

Miner Capacity

Container Type 

External Dimensions(L W H)

Weight-Net/Operation

Electrical

Max. Power Consumption

Input Voltage & Frequency

Network

Communication Protocol

Safety Certification

Container Certification

Fluid(Miner)

Water Capacity

Inlet/Outlet Temperature

Flow Rate

Operating Pressure

Coolant

Note: Customizable Design According to Specific Requirements

XS1000

100 Units

20 Feet High-Cube

6058 2438 2896mm

5900kg/8900kg

1000 kW

3Phase 380-480V 50/60Hz

5*24 Ports 100M Network Switch

Modbus TCP/IP

CE or CSA

China Classification Society Certification

450L

40°C/55°C @High Performance Mode

60m3/h

< 4Bar

Pure Water/Distilled Water + Special Corrosion Inhibitor +

Antifreeze (Select the Ratio According to the Freezing Point)

X Series Solution-1600kW

Technical Specification

image.png

Physical

Model 

Miner Capacity

Container Type 

External Dimensions(L W H)

Weight-Net/Operation

Electrical

Max. Power Consumption

Input Voltage & Frequency

Network

Communication Protocol

Safety Certification

Container Certification

Fluid(Miner)

Water Capacity

Inlet/Outlet Temperature

Flow Rate

Operating Pressure

Coolant

Note: Customizable Design According to Specific Requirements

XS1600

160 Units

20 Feet High-Cube

6058 2438 2896mm

8000kg/12800kg

1600 kW

3Phase 380-480V 50/60Hz

8*24 Ports 100M Network Switch

Modbus TCP/IP

CE or CSA

China Classification Society Certification

600L

40°C/55°C @High Performance Mode

96m3/h

< 4Bar

Pure Water/Distilled Water + Special Corrosion Inhibitor +

Antifreeze (Select the Ratio According to the Freezing Point)

X Series Solution-2400kW

Technical Specification

image.png

Physical

Model 

Miner Capacity

Container Type 

External Dimensions(L W H)

Weight-Net/Operation

Electrical

Max. Power Consumption

Input Voltage & Frequency

Network

Communication Protocol

Safety Certification

Container Certification

Fluid(Miner)

Water Capacity

Inlet/Outlet Temperature

Flow Rate

Operating Pressure

Coolant

Note: Customizable Design According to Specific Requirements

XS2400

240 Units

40 Feet High-Cube

12192 2438 2896mm

12000kg/19200kg

2400 kW

3Phase 380-480V 50/60Hz

12*24 Ports 100M Network Switch

Modbus TCP/IP

CE or CSA

China Classification Society Certification

1200L

40°C/55°C @High Performance Mode

144m3/h

< 4Bar

Pure Water/Distilled Water + Special Corrosion Inhibitor +

Antifreeze (Select the Ratio According to the Freezing Point)

bottom of page